BRAKING RESISTOR VALUES, POWERS, and CABLES for AE-LIFT,
AE-MAESTRO and AE-SMART to be used in lines
3x400V Table BR4

Rated Power

3kW

4kW

5.5 kW

7.5 kW

11 kW

15 kW

22 kW

30 kW

Rated Current

7A

9A

13A

18A

25A

32A

45A

60A

Braking Resistor Values

160 Ω

120 Ω

80 Ω

60 Ω

40 Ω

30 Ω

20 Ω

15 Ω

Minimum Resistor Power of Asynchronous Motor
(Car speed < 1.6m/s)

800 W
3x1.5mm

1.000 W
3x1.5mm

1.200 W
3x1.5mm

1.500 W
3x1.5mm

2.200 W
3x2.5mm

3.000 W
3x2.5mm

4.400 W
3x4mm

6.000 W
3x6mm

Minimum Resistor Power of Asynchronous Motor
(Car speed ≥ 1.6m/s)

1.000 W
3x1.5mm

1.500 W
3x1.5mm

1.800 W
3x1.5mm

2.250 W
3x2.5mm

3.300 W
3x2.5mm

4.500 W
3x2.5mm

6.600 W
3x4mm

9.000 W
3x6mm

Minimum Resistor Power of Synchronous Motor
(Car speed < 1.6m/s)

1.000 W
3x1.5mm

1.500 W
3x1.5mm

1.800 W
3x1.5mm

2.250 W
3x2.5mm

3.300 W
3x2.5mm

4.500 W
3x2.5mm

6.600 W
3x4mm

9.000 W
3x6mm

Minimum Resistor Power of Synchronous Motor
(Car speed ≥ 1.6m/s)

1.200 W
3x1.5mm

2.000 W
3x1.5mm

2.400 W
3x2.5mm

3.000 W
3x2.5mm

4.400 W
3x2.5mm

6.000 W
3x4mm

8.800 W
3x4mm

12.000 W
3x6mm

Minimum Resistor Power of Synchronous Motor
(Car speed ≥ 2.0m/s)
(Add FAN when car speed ≥ 2.5m/s)

1.500 W
3x1.5mm

2.500 W
3x2.5mm

3.000 W
3x2.5mm

3.750 W
3x2.5mm

5.500 W
3x2.5mm

7.500 W
3x4mm

11.000 W
3x4mm

15.000 W
3x6mm

Notes

  1. 3x…mmvalues stand for cable cross sections between the inverter and braking resistor.
  2. Select the braking resistor by taking the motor label into consideration, not inverter ratings.Inverter power and current may be greater than the ratings of the motor.Main reference should be motor current.
  3. Do not put the braking resistor into the controller box. It creates heat and may damage electronic boards.
  4. Do not forget to connect the metal housing of the resistor to earth. They may be high voltages across the resistor.
  5. Pay attention in connecting the braking resistor. Any short circuit in resistor or false connection may immediately will burn the inverter.
  6. If the drivers in 3x400V series are used as monophase (as 1x230V) or in tri-phase 200V line(3x200V)than select the appropriate resistor by looking at table BR2and taking the motor current as the main reference. In this case do not use table BR4.

AE-LIFT, BRAKING RESISTOR VALUES, POWERS, and CABLES for
AE-LIFT, AE-MAESTRO and AE-SMART to be used in lines
3x200V, 1x220V or 1x230V Table BR2

Rated Power

1.5kW

2kW

3kW

4kW

5.5kW

7.5kW

11kW

15kW

Rated Current

7A

9A

13A

18A

25A

32A

45A

60A

Braking Resistor Values

80 Ω

60 Ω

40 Ω

30 Ω

20 Ω

15 Ω

10 Ω

7.5 Ω

Minimum Resistor Power of Asynchronous Motor
(Car Speed < 1.6m/s)

400 W
3x1.5mm

500 W
3x1.5mm

800 W
3x1.5mm

1000 W
3x1.5mm

1.200 W
3x2.5mm

1.500 W
3x2.5mm

2.200 W
3x4mm

3.000 W
3x6mm

Minimum Resistor Power of Asynchronous Motor
(Car Speed ≥ 1.6m/s)

600 W
3x1.5mm

800 W
3x1.5mm

1.000 W
3x1.5mm

1.500 W
3x2.5mm

1.800 W
3x2.5mm

2.250 W
3x2.5mm

3.300 W
3x4mm

4.500 W
3x6mm

Minimum Resistor Power of Synchronous Motor
(Car Speed < 1.6m/s)

600 W
3x1.5mm

800 W
3x1.5mm

1.000 W
3x1.5mm

1.500 W
3x2.5mm

1.800 W
3x2.5mm

2.250 W
3x2.5mm

3.300 W
3x4mm

4.500 W
3x6mm

Minimum Resistor Power of Synchronous Motor
(Car Speed ≥ 1.6m/s)

750 W
3x1.5mm

1.000 W
3x1.5mm

1.500 W
3x2.5mm

2.000 W
3x2.5mm

2.400 W
3x2.5mm

3.000 W
3x4mm

4.400 W
3x4mm

6.000 W
3x6mm

Minimum Resistor Power of Synchronous Motor
(Car Speed ≥ 2.0m/s)
(Add FAN when car speed ≥ 2.5m/s)

750 W
3x1.5mm

1.200 W
3x2.5mm

2.500 W
3x2.5mm

2.500 W
3x2.5mm

3.000 W
3x2.5mm

3.750 W
3x4mm

5.500 W
3x4mm

7.500 W
3x6mm

Notes

  1. 3x…mmvalues stand for cable cross sections between the inverter and braking resistor.
  2. Select the braking resistor by taking the motor label into consideration, not inverter ratings.Inverter power and current may be greater than the ratings of the motor.Main reference should be motor current.
  3. Do not put the braking resistor into the controller box. It creates heat and may damage electronic boards.
  4. Do not forget to connect the metal housing of the resistor to earth. They may be high voltages across the resistor.